Effective and innovative technolo-
gy lays the foundation for highest
security standards
A new dimension in terms of reliability
and performance: Combining multi-
ple sensors in one unit the new
IQ8Quad detector generation is the
centrepiece in every fire alarm
system.
Irrespective of the application, the
IQ8Quad detector range provides
the ideal solution. The design of
each IQ8Quad variant is tailored to
different environmental conditions so
that the individual detection princi-
ples meet the respective require-
ments.
Easy installation and secure
investment
Despite its slim housing, the
IQ8Quad mounts on a large moun-
ting base, offering more wiring space
as well as simple linking options
within the base for wires that are not
in use.
Detectors can be simply replaced
without disconnecting the other loop
devices.
As a result, initial installation tests can be preformed before any IQ8Quad
detector is connected.
The IQ8Quad detector generation is tailored to the requirements of
IQ8Control and series 8000 control panels. When using tools 8000, the
detector topology is read and the data is stored within the system, allowing
remote programming and diagnosis.
IQ8Quad - the esserbus®detector
Powered loop - currently the most secure and economic form of alarm sig-
nalling: All system components are connected as fully addressable users
on one loop instead of being spread across different spurs. This allows
short and open circuit resilient power supply for alarm signalling devices
to be taken from the 2-wire analogue loop. Thus, various additional circuits,
transponders and power supply units become redundant and installation
time is reduced to an absolute minimum.
Up to 127 loop devices can be operated on one loop. Consequently, mixed
operation between IQ8Quad and series 9200 detectors is possibe.
•O - optical detectors for safe and early fire detection
•T - heat (temperature) detectors for detecting fires with both fast and
slow rise in temperatures
•O
2T - false-alarm-proof optical heat detectors for detecting
light and dark smoke in difficult environmental conditions
•OTG - optical heat detectors with built-in gas sensor for
detecting carbon monoxide
•Reliable and early fire detection with patented
multisensor technology
•Automatic adaptation to changing environmental
conditions
•Automatic monitoring of all sensors to guarantee
operational capacity and correct condition
•Short-circuit tolerant through integrated loop isolators
•Signal patterns of non-fire situations eliminated by
using special filter algorithms
•Integrated counters for fire,faults and operating time
•Easy installation and programming
•Efficient power management results in extremely
low battery capacity requirement in fire alarm panels
IQ8Quad

»»Ò³
Type
TM
TD
O
OT
OT
OTG
Part No.:
802171
802271
802371
802373
802374
802473
Operating voltage:
8 - 42 V DC
8 - 42 V DC
8 - 42 V DC
9 - 42 V DC
8 - 42 V DC
8 - 42 V DC
Quiescent current at UN approx.:
40 ?A
40 ?A
50 ?A
50 ?A
60 ?A
65 ?A
Max. area to be monitored:
30 m?
30 m?
150 m?
150 m?
150 m?
150 m?
Max. hight to be monitored:
7,5 m
7,5 m
12 m
12 m
12 m
12 m
Application temperature:
-20°C to +50°C
-20°C to +50°C
-20°C to +72°C
-20°C to +50°C
-20°C to +65°C
-20°C to +50°C
Response temperature (1°C /min):
+54°C to +65°C
+54°C to +65°C
-
+54°C to +65°C
+79°C to +88°C
+54°C to +65°C
VdS - No.:
G 204058G 204059G 204060G 205070G 204061G 205072
General technical data
Rated voltage:
19 V DC
Alarm current w/o communication:
approx. 18 mA
Storage temperature:
-25°C to +75°C
Type of protection:
IP 42
Material:
ABS
Colour:
white, similar RAL 9010
Weight:
approx. 110 g
Dimensions w/o base:
O=117 mm, H=49 mm
Dimensions base included:
O=117 mm, H=62 mm
Accessories IQ8Quad
Part No.
Standard detector base
805590
Detector base with relay contact
805591
Flush mount housing for detector base
805571
Label plate for detector base
805576
IP protection for detector base
805570
Further information is provided in our fire alarm catalogue.
Technical Data
P
ar
t
N
o.
7
97
96
1.
G
0
0
1/
20
06
T
ec
hn
ic
al
in
fo
rm
at
io
n
is
s
ub
je
ct
t
o
ch
an
ge
w
ith
ou
t
no
tic
e!
Input
Output
Output
esserbus® transponder
IQ8
Control M
Powered loop
IQ8Alarm
Detector with base
117
62
Schematic loop diagram:
Dimensions (mm):
Dieselstra?e 2, D-41469 Neuss
Phone:+49 (0) 21 37 / 17-0
Internet:
Email:
Fax:
+49 (0) 21 37 / 17-286
www.novar.de
info@novar.de
Novar GmbH a Honeywell Company
Fernkorngasse 10, A-1100 Wien
Phone:+43 (0)1 / 6 00 60 30
Internet:
Email:
Fax:
+43 (0)1 / 6 00 60 30-900
www.novar.at
austria@novar.com
Novar Austria GmbH

»»Ò³