The universalhigh-tech fire alarm controlpanel:
investmentprotection, scalabilityand
high-tech
l
The 8008 fire alarm computer meetsthe highestsafetystan-
dardsfor comprehensive fire monitoring. Asa universalfire alarm
controlpanel, ithasbeen designed for large buildingswith complex
safetyneeds. The option ofa second CPU makesitvirtuallyfault-
free. The 8008 conformsto allrelevantnationaland European stan-
dards.
Modular design and free configuration makesthe 8008 a flexible
device which can easilybe adapted to changing requirements. This
makesindividualplanning simple while allowing for future expan-
sion.
The esserbus
®, a short-circuitand wire-break-tolerantloop system,
offersmaximum reliabilityin operation and isa particularlycost-saving
investmentwith reduced wiring bycombined loop and spur topology.
Ordering details
PartNo.
8008 fire alarm computer:
Standard type S1 cabinet
768308
19" cabinet
768398
Extension housing S1E
768318
Package 8308
768428
Package 8308 with single zone indicator768418
Package 8308 with printer
768448
Package 8308 with single zone indicator
and printer
768408
Package 8318 with single zone indicator
and printer
768438
VdSapproval
G 293022
EN licence
G 296046
Productinformation
8008 fire alarm computer
Fi
re
a
la
rm
s
ys
te
m
s
Performance data ata glance
•Modular design, flexible configuration – easyto adaptto
changing requirements
•Double safetybyoptionalsecond CPU
•Up to 40 esserbus
®loops
•Simple to installand setup
•Error diagnosisatmodule level/automaticstatusanaly-
sis/remote diagnosisvia PC
•Conformsto allapplicable standardsand regulations
• Integrated controlpanelprinter; remote printer optional
•esserbus
®loop can be combined with spurs:
127 esserbus
®userscan be grouped into asmanyas
127 detector zones–for higher reliability, economyofscale
and flexibilityofplanning and application
•Networking ofmaximum 31 controlpanelsvia essernet
®

»»Ò³
Configuration formultiple applications
8008 fire alarm computer:
Uncompromising safety
Optionalsecond CPU
l
The core ofthe 8008 isa powerful16-bitCPU. The
modern hardware and software architecture allowsa
simple and flexible response to anysetofrequirements.
In certain applicationsa redundantsecond CPU isrequired
ifmore than 512 detectorsare connected, to ensure smooth
transition in case one CPU fails. Thisisstate-of-the-art
securityatitsbest.
Safe even ifcontrolpanelfails
Ifthe controlpanelshould fail, the monitoring loop
routesthe fire detection and alarm signalsto another point.
Even ifthe power fails, the available back-up batteryen-
suresthatthe system remainsactive. The 8008 remains
capable ofdetection beyond normalemergencyoperation.
Modular conceptprovidesscalability
The 8008 hardware supportsup to 40 micromodules.
Hence, the system iseasyto configure to the needsof
differentapplications.
Ring busfor flexibilityand safety
The ring bustechnologysupportschangesto the design
and use ofthe system even after initialset-up. The sen-
sorsofindividualdetectors/zonescan be switched on and
offmanuallyor bytime control. The esserbus
®transmits
faultand maintenance signalsin addition to alarms. More-
over, the exactlocation ofeach detector can be indicated
on the busbytextualinformation.
Connectsto mostadvanced detector types
Variousdetector typescan be connected to the 8008
fire alarm computer for all-round protection. Above all,
our leading edge multisensor fire detectorsoffer unsur-
passed fire detection in almosteveryconceivable case.
esserbus
®
The esserbus
®supportsa combination ofloopsand
spurswith up to 127 detectorsand esserbus
®transpon-
dersthatcan be grouped into asmanyas127 detector
zones. Even ifa wire breaks, alldetectorsin the loop will
be active and functioning. Onlythe section between two
isolatorswillautomaticallydisconnect.
The esserbus
®transpondersare bususerswith free-
programming inputsand outputsto activate and moni-
tor externaldevicesor connectstandard or diagnostic
detectors.
esserbus
®

»»Ò³
Productinformation8008 fire alarm computer
Simple central monitoring byremote diagnosisfunction
The 8008 identifiesautomaticallythe loop wiring and
determinesthe logicaddressesofthe bussubscribers. No
separate setting ofaddressesin the devicesisneeded.
essernet
®
The essernet
®supportsup to 31 devices, such as
controlpanels, indicating and operating panels, gateways
and computer-based intelligentdisplayterminalsin a
non-hierarchicalnetworkover greatdistances.
Messages, such asalarm, trouble, disconnectionsand
other eventsare available to allpanelsatanypointvia
essernet
®.
Simple to installand use
Installation and set-up are assimple asallour products.
Installation and set-up toolsensure rapid readinessofthe
system. Programming isdone via PC, connected directly
on the controlpanel.
To make operation easier, alldisplayscontain essen-
tialinformation. The essernet
®also supportslocaldevices.
Alarm and statusinformation can be displayed optional-
lybysingle zone indicator unitson the controlpanel,
localgraphicpanelsor textdisplaysor printed on a cen-
tralprinter or severalremote printers.
Telediagnosticprogram (TEDIS)
Unforeseen circumstancesoften require instantin-
formation on the cause ofa failure or maintenance case,
notallowing exactplanning ofservice missions, man-
power requirementsand technologydeploymentin ad-
vance. TEDISsolvesthisproblem.
The remote diagnosticprogram pollsand displaysall
importantdata on the controlpanel, and from 31 panels
via essernet
®:
•allcontrolpaneldata
•allcurrentstatusdata
•the statusofeach detector individually
•allcustomer-specificcorrelations
essernet
®

»»Ò³
Novar GmbH
Location Neuss:
D-41469 Neuss, Dieselstra?e 2
Tel.: +49(0)2137 171
Fax: +49(0)213717286
Art. No. 796649/03.2004
Technicalinformation issub-
jectto change withoutnotice
Internet:
www.novar.de
E-mail:
info@novar.de
Location Albstadt:
D-72458 Albstadt, Johannes-Mauthe-Stra?e 14
Tel.: +49(0)74318010
Fax: +49(0)74318011220
8008 fire alarm computer
Supplyvoltage
230 V/50–60 Hz/150 VA
Power supplyunit
12 V/7 A
Operating voltage
12 VDC
Quiescentcurrentconsumption
Max. 1 A
Currentfor externalconsumers
4 A
Emergencypower supply
12 V/max. 2 x40 Ah
Protection class
I DIN EN 60950 A1 and A2
Ambient
R14 DIN 50019
Operating temperature
0 °Cto 50 °C
Dimensions(WxH xD)
485 x619 x283 mm
Weight
Approx. 26 kg
Protection type
IP 30
Micromodules
Analogue loop module
Single ring line module for up to 127 series9200 intelligentfire detectorsor bussub-
(PartNo. 784382)
scribersgrouped in 127 zones; approx. 25 mA quiescentcurrent.
4-zone fire alarm module
4-zone card for connection ofautomaticand/or non-automaticstandard or diagnosticfire
(PartNo. 784381)
detectors; approx. 25 mA quiescentcurrent.
Master boxinterface module
Single MFAB interface module to activate and processfeedbackand acknowledge sig-
(PartNo. 784385)
nalsfor MFAB in continuousor intermittentmode; approx. 15 mA quiescentcurrent.
RS232/TTYmodule
Serialinterface module with RS232 or TTYformatoption, to use with externaldevices,
(PartNo. 784842)
e.g. IDT, printer, RIP; approx. 35 mA quiescentcurrentwith RS232, approx. 55 mA quies-
centcurrentwith TTY.
3-relaymodule
3-relaymodule with outputfunction; programming optionallyasNO or NCcontact;
(PartNo. 787531)
3xtwo-state “watchdog” relayoutput. Max. switch capacity: 1 A per output, 30 VDC;
approx. 5 mA quiescentcurrent.
3-relaycommon faultmodule
3-relaymodule with fixed functions, e.g. common fault, 2xtwo-state “watchdog”
(PartNo. 787532)
relayoutputwith free programming feature. Max. switch capacity: 1 A/30 VDC;
approx. 15 mA quiescentcurrent.
4-relaymodule
4-relaymodule with outputfunction; programming optionallyasNO or NCcontact;
(PartNo. 787530)
approx. 10 mA quiescentcurrent. Max. switch capacity: 1 A per output, 30 VDC;
max. 1 A each module.
essernet
®ring busmodule 62.5 kBd
Networkmodule for max. 31 devices, telephone line (I Y(ST) Yn x2 x0.8 mm),
(PartNo. 784840)
max. cable length: 700 m between 2 devices; approx. 170 mA quiescentcurrent.
essernet
®ring busmodule 500 kBd Networkmodule for max. 31 devices, cable IBM type 1 or equivalent;
(PartNo. 784841)
max. cable length: 1,000 m between 2 devices; approx. 150 mA quiescentcurrent.
Technicaldata